Building Automation System
Environmental protection instrument
News
BFC series controllers
BFC series controllers
(A)
(B)
Product Introduction
The BFC series controllers work on the MS/TP BUS specifiedbyBACnetprotocol, and communicate at up to 76.8Kbps.Thesecontrollers canseamlessly integrate with other companies’productscomplying withBACnet, and can be integrated into MODBUS,CBUS,PROFIBUS and othernetworks through the gateways or thethird-partyinterfaces.
Product Properties
Compatibility – Fully compatible with the BACnet,caninterconnectwith the products complying with BACnet protocol,andthe MS/TP BUScommunication speed can be up to 76.8Kbps.
Universality – Can freely program & download thecontrollogicaccording to the field control requirements.
Reliability – The application programs and hard-wares arestoredinthe nonvolatile storage to effectively ensure theprogramsafety.
Usability – Write the program with the graphicalfunctionmodules,easy-to-learn & use.
Rapidity – The program internal logical loop periodisonly100msec.
Technical Specification
Shell Material:
ABS (Engineering Plastic)
Outline Dimension: (H x W x D)
A Type: 165 x 140 x 40 mm
B Type: 112 x 140 x 40 mm
Mounting Position:
Wall or in-housing mounting
Terminal:
Pluggable Terminal
Environmental Requirements:
Temperature:
Working Temperature: 0 to 50 °C
Storing Temperature: -20 t0 60 °C
Humidity:
Working Humidity: 5 to 85% RH
Storing Humidity: 5 to 80% RH
Power Supply:
24VAC 50/60HZ
Communication:
BACnet MS/TP BUS, 76.8Kbps
Universal Inputs:
Input signal thermistor/dry contact, 0 to 10V, 4 to 20mA. 0 to5Visjumper-selectable
Digital Input:
Each loop input has the optoelectronic isolator.
Analog Output:
Output signals 0-10V & 4-20mA are jumper-selectable.
Digital Output:
Relay NO contact output, 277VAC 2A
24VDC Output:
One 24VDC output provides the DC power supply totheendequipments.
BACnet Support: Conforms to the AdvancedApplicationController(B-ASC) Standard Device Profile as defined,seethePICS.
Communication: The following ports are available on theBFCcontrolmodules:
EIA-485 port for MS/TP (9600 bps – 76.8 kbps).
Rnet Port supports:
1. Local access for system start-up and troubleshooting.
2. Local operator interface SIMView or TView.
3. RS Room Sensors - averaging or high/low select control.
Binary Outputs: 24VAC 50/60HZ
Universal Inputs:
1 BFC-322N Controller(A) 8 universalinputs(NTC10K,Drycontact,0-10V,4-20mA,0-5V);
8 binary inputs (Dry contact);
6 binary outputs(Dry contact,contact rated at 250VAC,3A)
6 analog outputs(0-10V or 4-20mA).
2 BFC-321N Controller(A) 8 universalinputs(NTC10K,Drycontact,0-10V,4-20mA,0-
5V);
8 binary inputs (Dry contact);
12 binary outputs(BO0-BO5 are Dry contact),contactratedat250VAC,3A.;
(BO6-BO11) is DC12V voltage output..need to connecttherelay.(12VDC)
3 BFC-312N Controller(B) 8 universalinputs(NTC10K,Drycontact,0-10V,4-20mA,0-5V);
4 binary outputs(Dry contact,contact rated at 250VAC,3A)
3 analog outputs(0-10V or 4-20mA).
4 BFC-311N Controller(B) 8 universalinputs(NTC10K,Drycontact,0-10V,4-20mA,0-5V);
6 binary outputs(BO0-BO3 are Dry contact),contactratedat250VAC,3A.;
(BO4-BO5) is DC12V voltage output..need to connect therelay(12VDC)1analog outputs(0-10V)
5 BFC-301N Controller(B) 4 universalinputs(NTC10K,Drycontact,0-10V,4-20mA,0-5V);
4 binary outputs(Dry contact,contact rated at 250VAC,3A)
2 analog outputs (0-10V)
6 BFC-302N Controller(B) 4 universalinputs(NTC10K,Drycontact,0-10V,4-20mA,0-5V);
6 binary outputs(Dry contact,contact rated at 250VAC,3A)
2 analog outputs (0-10V)
LED diaplay
7 BFC-323N Controller(A) 16 universalinputs(NTC10K,Drycontact,0-10V,4-20mA,0-5V);
6 binary outputs(Dry contact,contact rated at 250VAC,3A)
6 analog outputs(0-10V or 4-20mA).
Supported input types include: 0-5 V-dc, 0-10 V-dc,4-20mA,Thermistor (10k Ohm Type II), 1kOhm RTD (Platinum,NickelorBalco), and Dry Contact.
Memory: 1 MByte non-volatile battery-backed RAM, 1MByteFlashmemory, 16-bit memory bus. (Shelf life of the battery is10yearswith 10,000 hours of continuous operation.)
Real-time Clock: Battery-backed real-time clock.
Status Indicators: LED status indicators forEIA-485communication,running, error, power and all digitaloutputs.
Module Addressing: Rotary dip switches forintuitivenetworkaddressing of modules.
Protection: Built-in surge and transient protectioncircuitryforpower, communications, inputs and outputs.
Listed by: CE, EMC GB/T 17626
Environmental Operating Range: -20ºF to 140ºF (-29ºC to 60ºC);10to90% relative humidity, non-condensing.
NOTE: Control modules should be mounted inprotectiveenclosures.
Power Requirements: 24 V-ac ± 10%, 26 V-dc (25 V min, 30 Vmax),50to 60Hz, 20VA.
NOTE: Power consumption will increase when SIMVieworotheraccessories are attached.
Physical: Rugged aluminum cover. Removable screwterminalblocks.
Outline Dimension
(A) (B)